Transmitters of the “intrinsically safe or Zone 2 increased safety” type of protection can be installed in hazardous areas. The device meets the requirements of the EU Directive 2014/34/EU (ATEX), the FM and CSA regulations as well as other national approvals.
For the SITRANS TH320 without HART functionality, parameters are assigned with the PC. A special modem and the software tool SIPROM T are available for this purpose.
With HART communications interface:
The SITRANS TH320 is configured via HART. The configuration can be carried out using a handheld communicator or, more conveniently, with a HART modem and the SIMATIC PDM parameterization software. The configuration data is then permanently stored in the non-volatile memory (EEPROM).
After correct connection of input and supply voltage, the transmitter outputs a temperature-linear output signal and the diagnostics LED is green. In case of external errors, e.g. sensor short circuit or interruption, the LED flashes red; an internal device error is indicated by a permanent red light.
An ammeter can be connected at any time for checking and plausibility via the test terminals. The output current can be read without any interruption, or even without opening the current loop.