Endress+Hauser Flow-X IFLOWX flow computer

$6,600.00

The Flow-X flow computer provides gas volume conversion, event logging, parameter logging, and reports using state-of-the-art technology. Identical modules are combined in different housings, offering a multi-stream version Flow-X/P for 1 – 4 measuring distances with a local touch screen, or the version Flow-X/S for smaller installations with one measuring distance. It is the ideal partner for custody transfer gas metering solutions in installations with FLOWSIC600 ultrasonic gas flowmeters.

Flow-X IFLOWX flow computer

The ideal flow computer for gas metering with ultrasonic gas meters

Specs at a glance

  • Number of applications

    Support up to 4 gas runs or 2 liquid runs per module (Flow-X/M, Flow-X/C)

  • Inputs

    6x analog transmitter input, high accuracy
    Input types are 4 to 20 mA, 0 to 20 mA, 0 to 5 V, 1 to 5 V
    Accuracy mA inputs; 0.002% FS at 21 °C, 0.008% at full ambient range of 0-60 °C, long-term
    stability 0.01% per year
    Resolution: 24 bits. Analog inputs have the same earthing relative to all other electronic devices.

    16x digital status inputs. Resolution 100ns (10MHz)

  • Outputs

    4x analog output for process outputs and flow / pressure control. Resolution 14 bits, 0.075% FS.
    Analog outputs share same ground floating in relation to all other electronics.

    16x digital output, open collector. Rating 100mA @24V

Field of application

The Flow-X flow computer provides gas volume conversion, event logging, parameter logging, and reports using state-of-the-art technology. Identical modules are combined in different housings, offering a multi-stream version Flow-X/P for 1 – 4 measuring distances with a local touch screen, or the version Flow-X/S for smaller installations with one measuring distance. It is the ideal partner for custody transfer gas metering solutions in installations with FLOWSIC600 ultrasonic gas flowmeters.

  • Custody gas metering

  • Demanding natural gas and process gas applications


Device properties:

  • MID approved configuration for gas metering streams with FLOWSIC600

  • Powerful modules for demanding applications

  • Each module features CPU, memory and equal in/outputs

  • Intuitive user interface for graphics display and web browser

  • True remote access via Ethernet

  • Station computer for multiple streams

Benefits

  • Reduced planning and installation costs through standard configurations

  • Very accurate volume conversion with multiple calculation cycles per second

  • High reliability through independent modules with their own volume conversion and storage of measured values, counter readings and events

  • Easy extension of installations with modules featuring equal in/outputs and 100% software configuration

  • Reduced service and maintenance costs with tamper-proof remote maintenance

  • Cost-efficient and flexible system integration of multiple streams

Measuring principle

flow computer

Measuring variables

gas volume conversion, event logging, parameter logging, and reports

Number of applications

Support up to 4 gas runs or 2 liquid runs per module (Flow-X/M, Flow-X/C)

Calculations

Gas property calculations:
AGA 5, AGA 8 Part 1, AGA 8 Part 2 (GERG-2008), AGA 10
AGA NX-19
GERG-2008
GERG91mod (GOST 30319.2-1996)
GOST 30319.2-2015
GSSSD MR-113
ISO 6976, ISO 12213 Parts 2 and 3
S-GERG
Flow rate calculations:
AGA 3, AGA 7, AGA 9, AGA 11

Electrical connection

Voltage
24 V DC (± 10%), with redundant connections
Current consumption:
Flow-X/P0, X/M, X/S: ≤ 0.4 A nominal; ≤ 0.8 A maximal
Flow-X/C: ≤ 0.6 A nominal; ≤ 1.0 A maximal

Ambient temperature range

Flow-X/S: -40 °C … +75 °C
Flow-X/C, Flow-X/P, Flow-X/R: 0 °C … +60 °C

System

CPU and memory: 800 MHz, 512 MB RAM, 1 GB flash memory
Clock: Real-time clock, accuracy better than 1 sec/day
Gold cap for date and time retention
Watchdog: Hardware and software watchdog timer
Tamper switch: Mechanical tamper switch to prevent changing of the application and vital parameters within
that application

Supported gas chromatographs

Supports all common gas chromatographs (including ABB NGC8200 series, ABB BTU8100,
Danalyser, Yamatake HGC, Encal 3000, Angus GQA, Siemens Maxum and Sitrans)

Conformities

2014/32/EU Measuring Instruments Directive (MID)

Directive 2014/30 / EC relating to electromagnetic compatibility

2012/19/EU WEEE Directive (WEEE 2)

2011/65/EU RoHS

OIML R117-1

WELMEC 7.2, 8.3, 8.8

API 21.1

Hazardous area approvals

Applies for FlowX/M and X/S only
Class I, Division 2, Groups A, B, C, and D, T4
Class I, Zone 2, Group IIC, T4
IECEx Ex ec IIC Gc
ATEX II 3 G Ex ec IIC Gc

Inputs

6x analog transmitter input, high accuracy
Input types are 4 to 20 mA, 0 to 20 mA, 0 to 5 V, 1 to 5 V
Accuracy mA inputs; 0.002% FS at 21 °C, 0.008% at full ambient range of 0-60 °C, long-term
stability 0.01% per year
Resolution: 24 bits. Analog inputs have the same earthing relative to all other electronic devices.

16x digital status inputs. Resolution 100ns (10MHz)

Outputs

4x analog output for process outputs and flow / pressure control. Resolution 14 bits, 0.075% FS.
Analog outputs share same ground floating in relation to all other electronics.

16x digital output, open collector. Rating 100mA @24V